| Product Type | Automatic Voltage Regulator (AVR) |
| Model | AS540 |
| AVR Type | Analog, Self-Excited |
| Sensing | 2-Phase Sensing |
| Sensing Input Voltage | 95–130 VAC or 190–265 VAC, 1 Phase |
| Power Input Voltage | 95–265 VAC, 1 Phase |
| Input Frequency | 50–60 Hz |
| Maximum Power Output Voltage | 82 VDC at 200 VAC Input |
| Continuous Output Current | 4 A |
| Transient Output Current | 7.5 A for 10 Seconds |
| Voltage Regulation | ±1.0% RMS |
| Typical AVR Response | 20 ms |
| Field Current Response | 90% in 80 ms |
| External Voltage Adjustment | ±10% |
| Under-Frequency Protection | 94%–98% of Nominal Frequency |
| Unit Power Dissipation | Maximum 12 W |
| Over-Voltage Detection | 65 VDC Set Point |
| Compatible Alternator Range | Compatible STAMFORD S0 and S1 Alternators |
AS540 Automatic Voltage Regulator is an analog AVR designed for compatible STAMFORD alternators. It controls the alternator excitation system to help keep the generator output voltage stable.
The AS540 uses self-excited operation and also supports an optional auxiliary winding connection. It is designed for reliable voltage control in generator applications.
The AS540 can be used for compatible generator alternators where stable voltage regulation is required. It is suitable for diesel generator AVR replacement, alternator maintenance, and generator electrical repair work.
Before installation, check the alternator model, winding arrangement, voltage range, and existing AVR specifications to confirm compatibility.
The AVR senses the generator voltage and adjusts excitation as needed. This helps the alternator maintain a more stable output when the electrical load changes.
The AS540 supports 50–60 Hz operation. Its response time is designed for quick voltage correction. The unit also provides under-frequency protection and over-voltage detection for added operating control.
The AS540 is useful in applications where reliable generator voltage control is important. It can be used in industrial power systems, commercial generator sets, backup power systems, workshops, and generator service applications.
It is especially useful when replacing a compatible Stamford generator AVR during planned maintenance or repair.
The AS540 provides controlled alternator excitation with a typical AVR response of around 20 ms. Its specified voltage regulation is ±1% under the conditions stated by the manufacturer.
For replacement applications, always match the AVR with the correct alternator model and wiring configuration. Correct installation is important for safe and reliable generator operation.
Be the first to share your thoughts about this product!